SEL RTAC MCP Server

An MCP server for AcSELerator RTAC user logic. It lets an LLM client export a project to XML, read and edit POUs, GVLs and DataTypes, re-import the result as a new project, and get real compile errors back.

Why compiling goes through CODESYS

AcSELerator's own AcRtacCmd check returns check:0:success even when the logic has compile errors; the errors only appear in the GUI Output pane. So compile_logic copies the export's user logic verbatim into a fresh CODESYS project, adds generated SEL stubs, builds it headless, and returns each error with its object, section (interface/implementation), line and column. Because the text is copied unchanged, those positions match the RTAC source.

The stubs are generated from the export itself:

Stub Source
SEL types (SPS, MV, INS, STR, operSPC, operAPC, APC, SPC, quality/timestamp types) Hand-written in tools/sel_stubs.py
SEL functions/FBs (Sys_Time, ValidityCheck, TPUDO, TEX) Hand-written in tools/sel_stubs.py
Device tags (Greensmith_DNP.ISLAND_ENABLED, ...) Tag Name / Tag Type rows in device, tag-list and system XML
Tag aliases (SW1_52A3P) Tag Alias column
Tag Processor destinations (Tags.X) DestinationTagName / DTDataType
Device status objects (SCADA_DNP_POU.Offline, .EN) One per file under Devices/

The stubs are approximations of the SEL library. An error tagged "source": "stub" means a stub needs extending, not that the logic is wrong. Behaviour is not simulated; this is a type check.

Every user FB is instantiated in a generated harness program, so new FBs are checked even before anything calls them. RTAC itself skips unreferenced POUs.

Unit tests

run_unit_tests builds the export the same way as compile_logic, adds a generated runner program, downloads it to the CODESYS simulator and reads the results back. The runner steps through every case inside the PLC: set inputs, call the target for a number of cycles or a real-time hold, then compare the outputs against expected values.

{
  "target": "FunctionBlock1",
  "cases": [
    {
      "name": "request over limit is clamped",
      "steps": [
        {
          "inputs": {"Requested_kW": 100.0, "MaxAllowed_kW": 80.0, "Enable": true, "CommsHealthy": true},
          "expect": {"Limited_kW": 80.0, "LimitActive": true}
        }
      ]
    }
  ]
}
  • Targets: FunctionBlocks (a fresh instance per case), Programs (one instance, so state carries over between cases) and Functions (return / return.<field>).
  • Names: a name whose first segment the target declares (Enable, IID_com_delay.Q) refers to the target instance. Anything else is a global or device tag, written as-is (gv_SysIslanded, IID_CFG_MuGrdInputs_GRX_POU.Offline).
  • Values: true/false, numbers (compared within tolerance), or strings containing raw Structured Text ("T#5S", "validity_t.good", "'text'").
  • Timing: the simulator runs at about 20 ms per cycle, regardless of the configured task interval. Use hold_ms for timer behaviour, since it measures real time with TIME(), and leave a margin around timer presets.
  • Isolation: only the runner is scheduled. Other programs don't run, so anything they would normally write (globals, device tags) has to be set as a test input.
  • Results: pass/fail for every check, with the actual value. Errors in the test definition itself (a typo'd name, a wrong type) come back as compile errors with "source": "test".

Suites can be saved as JSON (one {target, cases} object or a list of them) and run with suite_file; see examples/FunctionBlock1.tests.json.

Tools

Tool What it does
rtac_status Is the background RTAC process running and logged in?
rtac_list_projects Projects in the AcRTAC database, with type and firmware version
rtac_export_project Export a project to an XML folder (read-only for the project)
rtac_import_project Import an XML folder as a new MCP_* project
rtac_delete_project Delete an MCP_* scratch project
list_logic_objects / get_logic_object Browse and read user logic
set_logic_object / create_logic_object Edit or add POUs, GVLs and DataTypes in the export
list_tasks / assign_program_to_task Task configuration (System/Main Controller.xml)
list_device_tags Device and tag-list tags with SEL types
compile_logic Type-check all user logic through CODESYS
run_unit_tests Run test cases against one POU in the CODESYS simulator and report pass/fail

The export/edit/compile tools work on a folder and don't need AcSELerator running. Only the rtac_* tools touch the AcRTAC database.

Safety rails

  • Imports only create new projects, and their names must start with MCP_ (RTAC_SCRATCH_PREFIX).
  • Deletes are refused for any project that doesn't start with that prefix.
  • There are no device tools (connect, send, firmware); nothing in this server talks to an RTAC.

Requirements

You only need the parts used by the tools you plan to run:

Requirement Needed for Notes
Windows everything AcSELerator and CODESYS are Windows-only
Python 3.10+ everything the mcp package needs 3.10 or newer; tested on 3.15
AcSELerator RTAC (with AcRtacCmd.exe) and access to an AcRTAC database (username and password) rtac_* tools (list, export, import, delete) Tested on 1.157. Not needed if you already have an exported XML folder
CODESYS 3.5 SP22 (standalone IDE, from the CODESYS Store) with the CODESYS Control Win V3 x64 device and the Standard library installed compile_logic, run_unit_tests Tested on SP22 Patch 4. This is separate from the CODESYS 3.5.10 embedded in AcSELerator, whose script engine can't be driven headless. Other versions should work if CODESYS_PATH, CODESYS_PROFILE and CODESYS_STANDARD_LIBRARY are set to match

run_unit_tests uses the CODESYS simulator, so it doesn't need a soft-PLC runtime license.

Setup

cd C:\Dev\rtac-mcp-server
python -m venv .venv
.venv\Scripts\python.exe -m pip install -r requirements.txt

Then register it with your MCP client as a stdio server. Most clients take a JSON entry like this:

{
  "mcpServers": {
    "rtac": {
      "command": "C:\\Dev\\rtac-mcp-server\\.venv\\Scripts\\python.exe",
      "args": ["C:\\Dev\\rtac-mcp-server\\server.py"]
    }
  }
}

Logging in to the AcRTAC database

The rtac_* tools run against a background RTAC process (alias rtacmcp), which must be logged in. Either set RTAC_DB_USER / RTAC_DB_PASSWORD in the server's environment, or log it in yourself after the server has started it:

& "C:\Program Files\SEL\AcSELerator\RTAC\AcRtacCmd.exe" login -a rtacmcp -p "<password>" <username>

Environment variables

Variable Default
ACRTACCMD_PATH C:\Program Files\SEL\AcSELerator\RTAC\AcRtacCmd.exe
RTAC_ALIAS rtacmcp
RTAC_SCRATCH_PREFIX MCP_
RTAC_DB_USER / RTAC_DB_PASSWORD unset (log in by hand)
CODESYS_PATH C:\Program Files\CODESYS 3.5.22.40\CODESYS\Common\CODESYS.exe
CODESYS_PROFILE CODESYS V3.5 SP22 Patch 4
CODESYS_DEVICE CODESYS Control Win V3 x64
CODESYS_STANDARD_LIBRARY Standard, 3.5.22.0 (System)
RTAC_MCP_WORK_DIR %TEMP%\rtac-mcp (each compile keeps its CODESYS project here)

Known limitations

  • importxml can't update a project in place, so every round trip makes a new project.
  • assign_program_to_task only appends to tasks that already have an explicit POU list. On a default-order task it changes nothing: a one-item list made RTAC move the devices and the Tag Processor to the end of the execution order on import. It appears that default-order tasks schedule programs automatically, but that hasn't been confirmed in the GUI.
  • Stubs are approximate (see above). Functions that nothing calls are still not compiled.
  • Tested against AcSELerator RTAC 1.157 (RTAC 3530 R146, 3350 R157) and CODESYS 3.5 SP22 Patch 4.